mm2, AWG and B&S: Cable Size Units Explained
Three labels appear on cable: mm², AWG and B&S. They all describe how thick the copper is, but they count it in different ways. Know which one you're looking at before you compare sizes.
mm²: the area of the copper
The label mm² means square millimetres. It gives the cross-section of the copper core, which is the area you'd see if you cut the cable across. Victron says cable core thickness is generally indicated in mm².1
Wikipedia says IEC 60228, used in most parts of the world, defines standard wire sizes based on their cross-sectional areas as expressed in mm².2
Bigger number, thicker copper, less resistance. That's the easy one.
AWG: American Wire Gauge
AWG works the other way round. A larger number means a thinner wire. Wikipedia says increasing gauge numbers denote logarithmically decreasing wire diameters.3
The scale also has a handy pattern. When the diameter of a solid round wire is doubled, the AWG decreases by 6.3
Thick sizes use zeros. A size such as 4/0 (also written 0000) is large. Victron's chart lists 4/0 at about 107 mm².1
B&S: Brown & Sharpe
B&S stands for Brown & Sharpe. Wikipedia says the company made the first attempt to adopt a geometrical system in 1855, and that this is now the American wire gauge.2
So a B&S number and an AWG number describe the same idea.2
If a cable is labelled B&S, check the packaging or the maker's own chart. This site hasn't saved a source on how B&S is used on cable sold locally, so it won't guess. Ask the seller for the size in mm² if the label is unclear.
Comparing the three
Victron's chart gives these conversions for cables up to AWG 10. It lists diameter, surface area and resistance for each size.1
| AWG | Surface area (mm²) | Resistance (ohm per metre) |
|---|---|---|
| 8 | 8.36 | 0.002061 |
| 6 | 13.3 | 0.001301 |
| 4 | 21.1 | 0.0008151 |
| 2 | 33.6 | 0.0005131 |
| 1/0 | 53.5 | 0.0003231 |
| 4/0 | 107 | 0.0001611 |
The pattern runs both ways. As the AWG number falls, the area rises and the resistance falls.1
A caution about matching sizes
Metric cables come in set sizes, and AWG sizes don't land exactly on them. A conversion gives the nearest match, not an identical one. As this site's own plain-sense note, when two sizes are close, the larger area has the lower resistance per metre, so check the maker's manual before choosing.
Look at the cable itself too. Victron notes that some cables have very thick insulation and may look thicker than they are. Check the marking or the specification for the real core size.1
Once every size is in the same unit, a cable chart helps you pick one. The worked calculation lets you check it.
Why the unit matters for voltage drop
Voltage drop depends on the copper's cross-section, so a size label only helps if you can turn it into an area. Victron's resistance column does that job. A cable with a bigger area has a smaller resistance per metre.1
Take two sizes from the table. The 8 AWG cable has 0.00206 ohms per metre, and 4 AWG has 0.000815. Over a 10 metre round trip, the first has 0.0206 ohms and the second has 0.00815 ohms, so the thicker cable loses less voltage at the same current.1
That's the whole reason sizes matter. Wrong unit, wrong guess, wrong drop. Write the area in mm² next to any size you plan to buy, and the later sums become easy.