Reading a 12V Cable Size Chart
A cable chart does the voltage drop sum for you. You give it amps and metres, and it gives back a size in square millimetres. The catch is that every chart is built on its own assumptions, and you need to know them before you trust it.
What the chart is built on
Check the notes under the chart first. Victron's table, for example, shows the maximum current for standard cables where the voltage drop is 0.259 volts.1
So that table isn't a general answer for every circuit. It fits one fixed drop. A different chart might use a bigger or smaller limit, and it will give different sizes for the same amps and length.1
Next, look at how length is counted. Victron's table uses the total cable length, which is the positive cable plus the negative cable.1
A real table
Here are some rows from Victron's table. The size is in mm², the usual unit for cable core thickness. The other columns give the maximum current in amps for a total cable length up to that many metres.1
| Cable size (mm²) | Up to 5 m | Up to 10 m | Up to 15 m | Up to 20 m1 |
|---|---|---|---|---|
| 1.5 | 4.5 A | 2.3 A | 1.5 A | 1.1 A1 |
| 2.5 | 7.5 A | 3.8 A | 2.5 A | 1.9 A1 |
| 4 | 12 A | 6 A | 4 A | 3 A1 |
| 6 | 18 A | 9 A | 6 A | 5 A1 |
| 10 | 30 A | 15 A | 10 A | 8 A1 |
| 16 | 48 A | 24 A | 16 A | 12 A1 |
Look at how the numbers move. Double the length and the allowed current halves. Double the cable size and it doubles. That matches the idea that a thin cable has higher resistance than a thick one of the same length.2
How to read it
Say a device draws 10 amps and sits 4 metres from the battery. The total length is 8 metres, so use the "up to 10 m" column.1
Go down that column until you reach a figure of 10 amps or more. The 6 mm² row gives 9 amps, which is too low. The 10 mm² row gives 15 amps, so it fits.1
If your length falls between columns, use the longer one. If your current falls between rows, use the bigger cable. Guessing the other way means a larger voltage drop than the chart promises.
What the chart leaves out
Victron's notes say the losses over the contacts aren't included. Connections, fuses, switches and crimps add resistance of their own.1
Victron's theory chapter says additional resistance is created by any items in the path the current has to flow through. A chart can't know how many you've fitted.2
The table also isn't a heat rating. A cable that passes a voltage drop check must still be able to carry the current without overheating, and a device's manual may name a size. Use the larger of the two answers.
Charts and units
Charts may list size in mm², in AWG or in B&S. Victron notes that cable core thickness is generally shown in mm², though other labels exist.1
One page sorts out the labels. Another shows the sum behind a chart.1